Pseudomonas in Augmented Care: What HTM 04-01 Asks Estates and IPC Teams to Do

TL;DR: Pseudomonas aeruginosa is an opportunistic bacterium that can colonise and infect vulnerable patients, and hospital water is a recognised source. HTM 04-01 Part C sets out extra controls for augmented care units such as critical care, neonatal, transplant and burns. The risk concentrates at the tap, especially in flow straighteners and the last two metres of pipework. The guidance covers pre-flush sampling, action at over 10 cfu per 100 mL, daily flushing of little-used taps with records, and careful basin and drain hygiene.

Last updated: 8 October 2026

Key takeaways

  • Pseudomonas aeruginosa is a Gram-negative bacterium found in wet environments. It is an opportunistic pathogen that can colonise and infect patients whose defences are weakened or breached.
  • HTM 04-01 Part C gives specific advice on Pseudomonas in augmented care, covering critical care, neonatal, renal, transplant, burns and other high-risk units.
  • The guidance says the organism is particularly evident within the last two metres before the point of discharge. Taps, flow straighteners, mixing valves and drains are the hot spots.
  • Outlets are sampled with a pre-flush sample, taken first thing after a period of no use. Counts over 10 cfu per 100 mL lead to a risk assessment on removing the outlet from service and further action.
  • Taps that are used infrequently on augmented care units should be flushed at least daily in the morning for one minute, with a record kept.
  • Continuous monitoring cannot detect Pseudomonas, but it can prove the controls happened: flushing, temperatures and outlet use.

What is Pseudomonas in augmented care, and why does water matter?

Pseudomonas in augmented care means the risk that Pseudomonas aeruginosa, a bacterium that thrives in water systems, colonises or infects the most vulnerable hospital patients. HTM 04-01 says hospital water is a recognised potential source, and that several outbreaks have been attributed to contaminated hospital water systems.

The organism is described in HTM 04-01 Part B, the operational management volume of the Health Technical Memorandum on safe water in healthcare premises. It calls P. aeruginosa a Gram-negative bacterium, commonly found in wet or moist environments, with the potential to cause infections in almost any organ or tissue, especially in patients compromised by underlying disease, age or immune deficiency. Its significance is made worse by its resistance to antibiotics and its ability to adapt to a wide range of environments.

It thrives in relatively nutrient-poor environments such as water systems, at a range of temperatures, and lives both in the water and in biofilms bound to surfaces. Part B lists the ways contaminated water can reach patients: drinking, bathing, contact with mucous membranes or a surgical site, splashing from outlets and basins, aerosols from respiratory equipment, equipment rinsed in contaminated water, and indirectly through staff hands washed in contaminated water.

Pseudomonas is a significant cause of serious infection in England. UKHSA’s quarterly epidemiological commentary reported 1,062 cases of P. aeruginosa bacteraemia from January to March 2026, a rate of 7.3 per 100,000 population, with 36.8% classed as hospital-onset healthcare-associated. Those figures cover all sources, and they do not say how many cases came from water.

Which units count as augmented care?

There is no fixed definition. HTM 04-01 Part C describes augmented care as units where patients are susceptible to invasive disease from opportunistic pathogens, and lets each provider designate its own. In broad terms that means severely immunosuppressed patients, patients needing organ support, and patients with extensive breaches in their skin.

HTM 04-01 Part C, the 2016 volume on Pseudomonas aeruginosa advice for augmented care units, sets out three broad patient groups:

  • patients who are severely immunosuppressed because of disease or treatment, including transplant patients during high-risk periods of their therapy;
  • patients cared for in units where organ support is necessary, such as critical care for adults, children and neonates, renal and respiratory units, which may include cystic fibrosis units, and other intensive care settings;
  • patients with extensive breaches in their skin who need contact with water as part of their care, such as in burns units.

Part C replaced a 2013 addendum to HTM 04-01 and is aimed at estates and facilities teams and infection prevention and control teams. It also notes its relevance to other waterborne pathogens, including Stenotrophomonas maltophilia, Burkholderia cepacia and atypical mycobacteria.

Augmented care patient groups under HTM 04-01 Part C: severely immunosuppressed patients, patients needing organ support, and patients with extensive skin breaches such as burns
Three broad patient groups. Each provider decides which of its units count.

Why is the tap the problem?

Because Pseudomonas concentrates at the very end of the system. HTM 04-01 Part B says that, unlike Legionella, its presence is particularly evident within the last two metres before the point of discharge. Taps, flow straighteners, mixing valves, solenoids and the drain below the basin all give it a place to grow.

Part B explains why. Devices fitted to or close to the tap outlet, such as mixing valves, solenoids and outlet fittings, can provide the conditions and nutrients that support microbial growth: suitable temperatures, a high surface area relative to the volume of water, and nutrients leaching from some materials, such as the rubber compound EPDM.

Some of the clearest evidence came from Northern Ireland. In December 2011 and early 2012 four neonates died from P. aeruginosa bacteraemia in hospitals there. A study published in the Journal of Hospital Infection by Walker and colleagues dismantled 30 taps and eight flow straighteners from the units into 494 components. The highest counts came from the flow straighteners, the metal support collars and the tap bodies around them, and tap isolates from two neonatal units had typing profiles consistent with strains from the tap water and the infected babies.

Part C draws the lessons into design advice. It notes that the move to single rooms with en-suite facilities, and more hand-wash basins to promote hand hygiene, has often led to infrequently used outlets with low water throughput, which carry a greater risk. There is some evidence that more complex outlet designs, such as some sensor-operated taps, are more prone to colonisation, and when selecting new taps, flow straighteners should be avoided where possible.

The drain matters too. Part C says waste-water drain outlets are particularly risky parts of the basin and are almost always contaminated, and that bacteria from patients, including antibiotic-resistant organisms, can seed the outlet and live in its biofilm.

Pseudomonas in augmented care concentrates in the last two metres of pipework: flow straightener, tap body, mixing valve, solenoid and the basin drain
The risk sits at the end of the system, where water meets the patient.

How should augmented care outlets be sampled?

With a pre-flush sample, taken from the tap first thing after a period of no use. HTM 04-01 Part B says outlets that supply water for direct patient contact, staff handwashing or filling and cleaning patient equipment should be sampled, using the first water delivered from the tap after at least two hours without use.

Appendix E of Part B sets out the method. The main strategy is to take the first sample of water, the pre-flush sample, at a time of no use, at least two hours or preferably longer, which normally means sampling in the early morning. The tap should not be cleaned or disinfected by heat or chemicals immediately before the pre-flush sample, because the aim is to find what is living in the outlet.

Sample bottles need a neutraliser, because disinfectants such as chlorine keep working after the sample is taken and could kill the bacteria before the laboratory counts them. Part B gives the example of 18 mg of sodium thiosulphate, enough to neutralise up to 5 mg/L of free chlorine, and warns that EDTA is ineffective for silver.

Comparing a pre-flush sample with a post-flush sample tells you where the problem is. Part B’s Table D1 says a high pre-flush count with a low post-flush count suggests a local problem at the outlet. High counts in both suggest a wider problem in the water system.

What do the results mean?

The actions follow three bands. If P. aeruginosa is not detected, there is no need to resample for six months unless the system or its use changes. At 1 to 10 cfu per 100 mL, the water safety group risk-assesses the use of the water while retesting. Above 10 cfu per 100 mL, it risk-assesses removing the outlet from service and investigates further.

Result, pre-flush sampleAction in HTM 04-01 Part B
Not detectedSatisfactory. No need to repeat sampling for six months unless the system, its configuration or occupancy changes
1 to 10 cfu per 100 mLThe water safety group risk-assesses the use of the water while retesting the outlet
Over 10 cfu per 100 mLRisk-assess removing the outlet from service, retest pre- and post-flush, and consider further sampling and an engineering survey

Part B’s Figure D1 suggests a retest sequence after remediation: retest at three days, reinstate the outlet if clear and retest after a further two weeks, then again after a further four weeks, before returning to sampling every six months. The water safety group can call for sampling sooner if there is clinical evidence that the water may be a source of colonisation or infection.

HTM 04-01 action levels for Pseudomonas aeruginosa: not detected, 1 to 10 cfu per 100 mL, and over 10 cfu per 100 mL, with the retest sequence at 3 days, 2 weeks and 4 weeks
Three bands, each with its own action and retest sequence.

What should happen every day?

Flushing, clean water for direct contact and careful basin hygiene. HTM 04-01 Part C says taps used infrequently on augmented care units should be flushed at least daily in the morning for one minute, with a record kept. Water in direct contact with patients should be of known satisfactory quality: tested free of P. aeruginosa, filtered at the point of use, or sterile.

Part C lists a set of practical controls that together reduce the chance of Pseudomonas in augmented care reaching a patient:

  • Water of known quality for direct contact. Either water where testing has shown absence of P. aeruginosa, water supplied through a point-of-use filter with a pore size of no more than 0.2 μm, or sterile water, for example for skin contact for babies in neonatal intensive care.
  • Daily flushing of little-used taps. At least daily in the morning for one minute, with a record. Taps can be programmed to flush automatically and the flushing recorded through the building management system.
  • No water features, chilled water or ice machines. Part C says these should not be installed in augmented care units, and that tap water should not be used in neonatal units to defrost frozen breast milk.
  • Basins used only for handwashing. No body fluids, no washing of patient equipment and no storage of used equipment in clinical wash-hand basins.
  • Clean the tap first. Taps should be cleaned before the rest of the basin, so the cloth does not carry contamination from the bowl or drain to the outlet.
  • Accurate records and drawings. Part C asks for up-to-date drawings of all hot and cold water systems, clear labelling, and trained staff for any work on outlets.

Behind all of this sits the water safety group, the multidisciplinary group that develops the water safety plan and advises on remedial action. Our water safety plan guide explains how the group and plan fit together.

Daily controls for augmented care units from HTM 04-01 Part C, including flushing, water of known quality, basin hygiene and records
Most of the protection comes from routine done every day and written down.

What if contamination is found?

Act as a team, keep the outlet flushing and find the cause. HTM 04-01 Part B says the water safety group should hold a focused incident control meeting with infection control, estates and clinical staff. An outlet taken out of service should still be flushed daily, and flow straighteners, splashing, dead-legs and little-used outlets should all be investigated.

Paragraph D22 of Part B lists the measures to consider:

  1. Inform the water safety group and hold a focused incident control meeting to prioritise patient safety and agree an action plan.
  2. Continue daily flushing of an outlet taken out of service, to stop the water stagnating and the contamination getting worse.
  3. Consider removing flow straighteners where practical, bearing in mind this can cause splashing.
  4. Investigate splashing, which can spread organisms: a tap flow that does not suit the basin, water falling straight into the waste, the wrong height between tap and basin, excess pressure or a blocked flow straightener.
  5. Supplement handwashing with antimicrobial hand-rub.
  6. Check for infrequently used outlets and consider removing them, such as showers in areas where patients are mostly confined to bed.
  7. Check that the hot connection to a mixing tap is not fed from an upstream thermostatic mixing valve.

Part B also describes how to read the pattern across a unit. A few positive outlets among many negative ones point to a source at or near those outlets. Positive results across most outlets point to the water services themselves.

Where does monitoring help?

In proving the controls happened. Continuous monitoring cannot detect Pseudomonas, which needs laboratory testing. It can track hot and cold water temperatures at outlets, show when flushing happened or was missed, flag stagnation, and give the water safety group an audit-ready record in place of paper sheets.

HTM 04-01 already allows automatic flushing recorded through the building management system. AQUAIOT’s Legionella monitoring tracks temperature profiles at tanks, loops and sentinel outlets, raises alerts when temperatures drift into risk zones or flushing is missed, and keeps audit-ready trails that can be exported or shared with BMS and CAFM systems. The same records support the daily flushing and record-keeping that Part C asks for on augmented care units.

We see monitoring as evidence alongside sampling. The water safety group still needs pre-flush samples, laboratory results and engineering surveys. What monitoring adds is a continuous, time-stamped picture of how each outlet is used and maintained between samples. Our page on HTM 04-01 monitoring and our NHS water management guide cover the wider estate. To discuss a unit or a trust, speak to an expert.

Monitoring record for augmented care outlets showing daily flushes logged per tap, one missed flush flagged and temperatures tracked for the water safety group
Monitoring cannot see Pseudomonas. It can show every flush, every temperature and every gap.

Frequently asked questions

What is augmented care?

There is no fixed definition. HTM 04-01 Part C uses it for units where patients are especially vulnerable to opportunistic infection, broadly severely immunosuppressed patients, patients needing organ support such as critical and neonatal care, and patients with extensive skin breaches such as burns. Each provider designates its own units.

How often should augmented care water outlets be sampled for Pseudomonas?

HTM 04-01 Part B says that if P. aeruginosa is not detected, there is no need to repeat sampling for six months unless the system, its configuration or occupancy changes. The water safety group can require sampling sooner where there is clinical suspicion that water is a source of infection.

What is the action level for Pseudomonas aeruginosa in hospital water?

Under HTM 04-01 Part B, a count of 1 to 10 cfu per 100 mL leads the water safety group to risk-assess the water’s use while retesting. Over 10 cfu per 100 mL, it risk-assesses removing the outlet from service, retests and considers further sampling and an engineering survey.

Why are flow straighteners a problem?

Their large surface area relative to the water passing through gives bacteria room to grow. In the Northern Ireland neonatal investigation, the highest P. aeruginosa counts came from flow straighteners, their metal support collars and the surrounding tap bodies. HTM 04-01 Part C advises avoiding them where possible when selecting new taps.

How often should taps in augmented care be flushed?

HTM 04-01 Part C says taps that are used infrequently on augmented care units should be flushed at least daily in the morning for one minute, with a record kept of when they were flushed. Automatic flushing can be recorded through the building management system.

One last thought

Most water safety work in a hospital happens far from the patient, in tanks, calorifiers and plant rooms. Pseudomonas in augmented care is different. It lives in the last two metres, in the tap the nurse uses and the basin beside the cot, which is why the controls are so practical and so daily.

The guidance is clear about what works: the right taps, clean water for direct contact, daily flushing, careful cleaning, pre-flush sampling and fast action on results. The hardest part is doing all of it every day, on every unit, and being able to prove it.