Technology House, Stratfield Park, Waterlooville, PO7 7XN 023 9223 3611

Telemetry, data and integration

What is the WITS protocol in water telemetry?

Short answer

WITS is an open telemetry standard that defines how a field outstation and a master telemetry station exchange data, built as a profile on top of DNP3. It started life in the UK water industry as the Water Industry Telemetry Standards and is now maintained as the Worldwide Industrial Telemetry Standards. Its purpose is procurement rather than performance: it lets a utility buy outstations from more than one supplier and still have them work with the master station it already owns.

  • It is a profile on DNP3. Not a new protocol invented from nothing, but a defined way of using an established one.
  • The point is breaking lock-in. Interchangeable outstations, so replacing a master station does not mean replacing the field estate.
  • It works by exception. The outstation reports changes and buffers through comms outages rather than waiting to be polled.
  • It is not a radio or a platform. WITS sits above the bearer. It says nothing about whether you use cellular, LoRaWAN or a fixed line.

The problem it was built to solve

Telemetry estates used to be single-supplier by default. Each vendor’s outstations spoke their own dialect to their own master station, and the two were bought together. Once a utility had a few thousand of them in the field, the master station could not realistically be replaced, because replacing it meant replacing everything it talked to.

WITS exists to break that. By defining the exchange between outstation and master station in the open, it makes the field device a commodity that can be bought competitively. An outstation from one supplier can be adopted by a master station from another, and a utility can change either end without stranding the other.

That is a procurement argument rather than a technical one, which is why WITS turns up in framework specifications and tender documents far more often than it turns up in engineering conversations.

How it works

WITS is built on DNP3, a protocol already widely used across utilities for supervisory control and data acquisition. What WITS adds is a defined configuration and behaviour model on top, so that two devices do not merely speak the same words but use them the same way: how the outstation is configured remotely, how readings are timestamped, how alarms and analogue and digital points are represented, and what happens when communications fail.

The behaviour that matters most in the field is reporting by exception with a store-and-forward buffer. Rather than being polled continuously, the outstation sends data when something changes or on a defined schedule, which suits a battery-powered asset on a cellular connection. When the connection drops it holds readings locally and forwards them once the link returns, carrying their original timestamps rather than leaving a gap in the record. For anything used as evidence later, that distinction between a missing reading and a late one is the whole point.

Where it matters, and where it does not

WITS matters if you are a water company, or supplying into one, and the data has to arrive in an existing master station or SCADA system. In that world it is often a hard requirement in the specification, and a device that cannot meet it is out regardless of how good the measurement is.

It matters much less on a private estate, a council site or a facilities portfolio with no master station and no SCADA. There the data goes to a cloud platform over an API or MQTT, the interoperability problem WITS solves does not exist, and specifying it adds cost and configuration for a benefit nobody will use. On those sites the useful questions are about how the device reports and how often, not which telemetry standard it carries.

It is also worth being clear about what WITS is not. It is not a radio technology, not a cellular standard, and not a data platform. It defines the conversation, not the medium it travels over and not the software you look at afterwards.

What to ask a supplier

The word WITS on a datasheet is not by itself an answer, because the standard has versions and because conformance is specific.

Ask which version is supported. Ask for the conformance testing evidence and which master station it was tested against, since interoperability is proven in pairs rather than asserted in general. Establish whether the claim covers the outstation, the master station or both, as they are separate pieces. Then check that the bearer suits the site, because a standard-compliant outstation is no use where there is no signal.

If your specification names WITS, tell us at enquiry stage and we will confirm what the specific outstation proposed for your scheme supports, rather than answering in general terms.

What AQUAIOT uses for this

The solutions and hardware that apply to the question above.

Sources

  1. WITS Protocol Standards Association. https://www.witsprotocol.org/